Specifications |
Insulation Tests |
Test Voltage |
250 / 500 / 1000 Volts DC |
Measurement Range |
1 to 11 MW, 11 to 500 MW / 10 to 110 MW, 110 to 5000 MW |
Short Circuit Current |
5 mA approximately |
Accuracy |
2 percent of full scale |
Automatic Discharge |
8 s/µF |
Charging Time |
0.2 s/µF / 0.5 s/µF |
Voltage Warning Indicator |
Amber LED indicates crank speed and proper test voltage |
Voltage Tests |
Measurement Range |
0 - 600 Volts AC |
Accuracy |
3 percent of full scale |
Display |
Analog Display |
Rugged taut band suspension |
General Specifications |
Power Source |
Hand cranked |
Dielectric Test |
2000 Volts 50-60 Hz, between (-), (+), and ground terminals |
Dimensions |
4.7 x 4.7 x 5.1" (120 x 120 x 130 mm) |
Weight |
3.3 lbs (1.5 kg) |
Temperature Range |
64 ° to 75 °F (18° to 24°C), 30 - 50 Percent RH |
Operating Range |
14° to 122°F (-10° to 50°C), 0 - 80 Percent RH |
Storage Range |
-4°F to 176°F (-20° to 80°C), 0 - 90 Percent RH |
Case |
Cast aluminum alloy case and lod painted safety yellow, with heavy duty gray polycarbonate front panel;
O-ring sealed between case and front panel; sealed against ; folding crank |
Terminals |
"+" Line (red); "-" earth (black); accept standard 4mm safety bannana plugs; ground accepts
4 mm spade lugs or bannana |
Safety Reference Specifications |
Safety Ratings |
IP54 with lid, IP52 without lid, VDE413 part 1/4 except f, IEC414, IEC529, MIL-T-38800D, IEC51 |
Agency Approvals |
CE Mark |